Description
TOA VX-3008F AMQ VX-3000 Main Frame, Up To 3 VX series amplifiers (8 Zones Switching Between 2 Amps + Standby Amp)
Product Details
The VX-3008F is a rack-mount voice alarm system frame for the VX-3000 Series, with eight monitored speaker outputs and three module slots.
It takes VX-015DA, VX-030DA and VX-050DA amplifier modules, with two slots when a line output module is fitted, and carries the mandatory EN54-16 indications. Inputs are four audio and 16 contact, over dual LAN ports, and it is powered from 20 – 33 V DC. It measures 483 × 132.6 × 345 mm and weighs 7.9 kg.
Features
- Up to 3 amps (8 zones switching between 2 amps + standby amp or 8 zones freely assignable to 1 of 2 amps)
- All mandatory indications by EN54-16
- Status indication for each speaker line
- Fault acknowledge and lamp test button
- Input DSP: flexible filtertypes and compressor
- Output DSP: flexible filtertypes, compressor and delay up to 2.7 sec.
- Frame for 3 amplifier modules with 8 monitored speaker outputs.
- Two amplifier modules can be assigned to any speaker output.
- Speaker outputs with overlapping amplifiers will automatically choose the amplifier which signal has to be transmitted.
- This allows a simultaneous broadcast of two different audio signals per frame to achieve an interruption-free BGM operation during a paging.
- The third amplifier module can be used as standby amplifier.
- Up to 4 base frames of this type can be cascaded to increase the number of assignable speaker outputs.
- Monitoring is possible by impedance surveillance or by using an end-of-line module.
- Settings for impedance deviation to indicate an open or shorted line can be individually set for every output.
- 4 general balanced audio inputs (microphone/line level) and 2 inputs for up to 8 remote microphones including up to two emergency microphones.
- The signals at the general audio inputs can be mixed.
- All mandatory indications and controls regarding EN54-16 can be found on the front panel.
- Fault indication for every speaker output line.
- Redundant network connection (Ethernet) of the base frame with RSTP via two RJ45 ports.
Specifications
| Technical | |
|---|---|
| Model | VX-3008F |
| Order Code | VX-3008F AMQ |
| Power Source | 20 - 33 V DC, removable terminal block (4 pins) |
| Power Consumption | 24 W (frame only) at 33V DC input, 90 W (RS Link: 2 A output) at 33 V DC input |
| LAN A, B | Number of Connectors: 2 (LAN A, LAN B); Network I/F: 100BASE-TX; Network Protocol: TCP, UDP, ARP, ICMP, RTP, IGMP, FTP, HTTP, NTP; Spanning tree Protocol: RSTP; Audio Transmission System: TOA Packet Audio(*1); Audio Encoding Method: PCM; Audio Sampling Frequency: 48 kHz; Audio Quantifying Bit number: 16 bits; Connection Device: VX-3004F, VX-3008F, VX-3016F, NX-300, VX-3000PM, VX-3000CT, and Switching HUB; Connector: RJ45 connector; Connection Cable: Category 5 twisted pair cable (CAT 5) or greater; Number of Stages of Cascade connection: Up to 7; Maximum Cable Distance: 100m (328.08 ft) |
| RS Link A, B | Number of Connectors: 2 (RS LINK A, RS LINK B); Audio input level; 0 dB (*2); Power feed: Max. 1 A per connector; Connector: RJ45 connector; Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP) or greater; Maximum cable distance: 1200 m (3937.01 ft) |
| DS Link | Connection Device: DS LINK of Power supply units; Connector: RJ45 connector; Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP); Maximum Cable Distance: 5 m (16.4 ft) |
| Analog Link | Number of Connectors: 1 input, 1 output; Connection Device: VX-3004F, VX-3008F, VX-3016F; Connector: RJ45 connector; Connection Cable: Shielded Category 5 twisted pair cable (CAT5-STP) or greater; Maximum Cable Distance: 800 m (2624.67 ft) |
| Audio Input 1, 2, 3, 4 | 4 inputs; Sensitivity Line: -20 dB(*2)/ MIC: -60 dB(*2); LINE/MIC/ANC sensor (changeable with setting software); Gain Control: volume adjustable with volume control (internal front panel) -∞ to 0 dB; Input Impedance: 47kΩ electronically-balanced; Frequency Response: 40 Hz - 20 kHz ±1 dB (at DA CONTROL LINK, 0 dB output); Distortion: 1% or less (at DA CONTROL LINK, 0 dB output, 1 kHz); Signal to Noise Ratio: 60 dB or more (at DA CONTROL LINK, A-weighted); Phantom Power Supply: 24 V DC, can be set with setting software; Connector: Removable terminal block (6 pins): 2 |
| Audio Input (second row as printed) | 16 inputs, no-voltage make contact input, open voltage: 24 V DC; short-circuit current: 2 mA; Fault Detection System: Short circuit, Open circuit; Method: Voltage detect; Connector: RJ45 connector |
| Control Input 1, 2 | 16 inputs , no-voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA; Fault Detection System: Short circuit, Open circuit, Method: Voltage detect; Connector: RJ45 connector; Connection Cable: Shielded Category 5 twisted pair cable (CAT5_STP) or greater |
| Emergency Control IN | Input 2: Isolated voltage input, -24 to +24 V; Connector: RJ45 connector; Connection Cable: Category 5 twisted pair cable (CAT5) or greater |
| VOX Function | Threshold: –60 to 0 dB (1 dB steps); Hysteresis: 0 to +10 dB; Hold time: 10 ms – 10 s; Settable for each audio input |
| Control Output 1, 2 | General outputs : 8 with CONTROL OUTPUT 1; Exclusive outputs : 3 with CONTROL OUTPUT 2; GENERAL FAULT, CPU FAULT, CPU OFF; No-voltage make contact, electrical contact output, control current: 10 mA ; withstand voltage: 28 V DC; Connector: RJ45 connector; Connection cable: Shielded Category 5 twisted pair cable (CAT5-STP)- or greater |
| ATT/Control Output | 8 outputs, no-voltage make contact, relay contact (NC, NO, C), control current: 2 mA to 5 A; withstand voltage: 125 V AC, 40 V DC; Connector: Removable terminal block (12 pins) x 2 |
| Digital Signal Processing — Feedback Suppressor (FBS) | 7 filters (auto); Settable for each audio input and RS LINK (A/B) |
| Digital Signal Processing — Equalizer/Filter | 3 bands for each audio input and RS LINK (A/B), 6 bands for each amplifier output; Parametric equalizer: 20 Hz - 20kHz, ±15 dB, Q 0.267 - 69.249; Filtering: High-pass filter 20- Hz - 20 kHz, 6 dB/oct, 12 dB/oct; Low-pass filter 20- Hz - 20 kHz, 6 dB/oct, 12 dB/oct; High shelving filter 6 - 20 kHz, ±15 dB; Low shelving filter 20 - 500 kHz, ±15 dB; Notch filter (amplifier output only) 20 Hz - 20 kHz, Q: 8.651 - 69.249; All-pass filter (amplifier output only) 20 Hz - 20 kHz, Q: 0.267 - 69.249; Horn equalizer (amplifier output only) 20 kHz, 0 to +18 dB (0.5 dB steps) |
| Digital Signal Processing — Compressor | Threshold: -20 to 0 dB (1 dB steps); Ratio: 1:1, 1.1:1, 1.2:1, 1.3:1, 1.5:1, 1.7:1, 2:1, 2.3:1, 2.6:1, 3:1, 4:1, 5:1, 7:1, 8:1, 10:1, 12:1, 20:1, ∞:1; Attack time: 0.2 ms - 5 s, Release time: 10 ms - 5 s; Gain: -∞ to +10 dB, Knee type: hard knee, middle knee, soft knee |
| Digital Signal Processing — Delay | For each amplifier output, 0 - 2730 ms (0.021 ms steps) |
| ANC (Ambient Noise Control) | Amplifier output level control, Automatic sensor input reference level measuring, Sensor input reference level fine adjustment Maximum output signal level control: -15 to 0 dB; Minimum output signal level control: -18 to -3 dB; Sample time setting: 10 s, 20 s, 30 s, 1 min, 5 min; Gain ratio setting: (Ambient noise: Output signal level) 6:3, 5:3, 4:3, 3:3, 3:4, 3:5, 3:6; Ambient noise measuring frequency setting: 20 Hz - 20 kHz, 3 points |
| Program Timer | Weekly program method; Daily program: 50 events, 10 types; Holiday program: 50 types |
| Time Adjustment | Control input, NTP |
| Speaker Line | 8 channels; 1 Earth terminal; Max. Voltage/Current: 100 VRMS, 5 ARMS; Connector: Removable terminal block (17 pins):1; Fault detection system: Short circuit, Open circuit, Ground fault, Method: Impedance or End of line |
| Standby Amplifier Input/Output | Input: 1, Output: 1; Max. Voltage/Current: 100 VRMS, 5 ARMS; Connector: Removable terminal block (2 pins) x 2 |
| Extension Amplifier Input/Output | Input: 2, Output: 2, Max. Voltage/Current: 100 VRMS, 5 ARMS, Connector: Removable terminal block (2 pins) x 4 |
| Module Slot | Number of modules: 3 (when the line output module is installed: 2); DA CONTROL LINK: 3; DA OUTPUT LINK: 3 (Used only when a power amplifier module is installed) |
| Indicators | POWER (green): 1, RUN (green): 1, EMERGENCY (red): 1, CPU OFF (red): 1, LAN A (green): 1, LAN B (green): 1, RS LINK A (green):1, RS LINK B (green):1; FAULT STATUS (yellow) GENERAL: 1, UNIT: 1, NETWORK: 1, EMG MIC: 1, FUSE: 1, POWER: 1, CPU: 1, ZONE: 8; AMPLIFIER PEAK (red): 3, SIGNAL (green): 3, OPERATE (green): 3, POWER (green): 3 |
| Operation | Fault control switch: 2 (ACK/RESET); Test Switch: 1 (LAMP TEST); Setting Switch: ID NUMBER, RESET, IMPEDANCE, Setting (internal front panel) |
| Operating Temperature | -5°C to 45°C (23°F to 113°F) [datasheet prints: −5 °C to +45 °C (23 °F to 113 °F)] |
| Operating Humidity | 90%RH or less (no condensation) |
| Physical | |
|---|---|
| Finish | Panel: Surface-treated steel plate, black, 30% gloss, paint [datasheet prints "30% glossy, paint"] |
| Dimensions | 483 x 132.6 x 345 mm [datasheet: 483 (W) x 132.6 (H) x 345 (D) mm (19.02" x 5.22" x 13.58")] |
| Weight | 7.9 kg [datasheet: 7.9 kg (17.42 lb)] |
| Supplied Accessories | VX-015DA System Amplifier — https://www.toaelectronics.com/en-us/products/detail/vx015daamq; VX-030DA System Amplifier — https://www.toaelectronics.com/en-us/products/detail/vx030daamq; VX-050DA System Amplifier — https://www.toaelectronics.com/en-us/products/detail/vx050daamq |
Specifications subject to change.