TOA VM-3240VA AMQ Voice Alarm System Master 240W w/UL 2572/864

TOASKU: VM-3240VA AMQ

Price:

Login to see pricing

MSRP:
$5,180.00

Description

TOA VM-3240VA AMQ Voice Alarm System Master 240W w/UL 2572/864

Product Details

The VM-3240VA is the 240 W voice alarm system amplifier and controlling unit of the VM-3000 Series, certified to UL 2572 and CAN/ULC-S576.

It has four mic/line inputs, two BGM inputs, six speaker outputs, two remote microphone links, a network port and eight control inputs and outputs. A system takes up to nine VM-3240E extension amplifiers. Power is 120 V AC, 60 Hz. It measures 482 × 132.6 × 431.2 mm and weighs 16.5 kg. A hand-held emergency microphone, setting software CD and link cables are supplied.

Features

  • Max. 13 MIC/LINE Inputs
  • Max. 60 assignable speaker zone outputs
  • Up to a combination of 4 Fireman's and remote Microphones
  • Continuous speaker line monitoring without interruption
  • Complete fault detection and indication
  • Built-in voice alarm message
  • Max. 13 MIC/LINE Inputs (Max system comprises 1x VM-3240VA: 4 MIC/LINE Inputs, 9x VM-3240E: 9 Local Inputs)
  • 2 BGM inputs - VM-3240VA
  • Up to a combination of 4 Fireman's and remote Microphones (max. 2 Fireman's Microphones)
  • Max. 60 assignable speaker zone outputs (6 outputs per amplifier)
  • BGM volume setting possible for each zone
  • Digital audio processed & controlled
  • Full digital audio mixing (DSP)
  • Built-in high quality electronic voice message
  • Intuitive configuration
  • Zone setting, priority setting, failure detection setting by dedicated PC software
  • LCD display of current status and configuration setting of system units
  • Emergency Functions: Continuous speaker line monitoring without interruption of BGM distribution or paging announcements; Complete fault detection and indication; Off-site log check capability via LAN; Built-in and remote Fireman's Microphones; Built-in voice alarm message; 2-Phased voice alarm message (Alert and Evacuation) broadcasting
  • Paging Functions: 2 Remote Microphone interface lines; Paging (All zones/Group/Individual); 2-channel broadcast with external amplifier (Paging/BGM), VP-2241 (240W x 1) Power Amplifier
  • Power Source: 120 V AC, 60 Hz
  • Power Consumption: Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) ["Power Consumption" is duplicated inside the value as printed]
  • Rated Output: 240 W
  • Frequency Response: 50 Hz - 20 kHz, ±3 dB (at 1/3 rated output)
  • Distortion: 0.7 % or less (at rated output, 1 kHz)
  • Signal-to-Noise Ratio: 85 dB or more
  • Audio Input/Output Characteristic: Sampling frequency: 48 kHz; A/D D/A converter: 24 bit
  • Input: Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack; Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins); BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack; External amplifier input: 100 V line, removable terminal block (14 pins)
  • Output: Speaker output 1 - 2: Max. (240 W) per output; Speaker output 3 - 6: Max. (120 W) per output; Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins); Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection; Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins); Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
  • RM Link: Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector; Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
  • Network I/F: 10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector; Maximum distance: 100 m (109.36 yd) between this unit and a switching hub; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
  • VM Link: Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector; Maximum distance: 800 m (874.89 yd); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
  • EXT PA Link: Connecting the VP-2241 or VP-2421, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
  • General Control: Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins); Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins)
  • Emergency Control: Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector; Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector; Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector
  • ATT Control: Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins)
  • Power Input/Output: Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC); PS out: 28 V DC/18 A; M4 screw terminal, distance between barriers: 11 mm (0.43")
  • DC24V Output: 24 V DC, Maximum feeding current 0.3 A
  • DS Link: Connecting the VX-2000DS, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
  • Operating Temperature: -5 °C to +45 °C (23 °F to 113 °F)
  • Operating Humidity: 5 % to 95 %RH (no condensation)
  • Finish: Panel: Aluminum, hairline, black; Case: Surface-treated steel plate, black, paint
  • Dimensions: 482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98")
  • Weight: 16.5 kg (36.38 lb)
  • Included Accessories: Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1
  • Power Source: 120 V AC, 60 Hz (agrees)
  • Power Consumption: 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) (agrees)
  • Rated Output: 240 W, 21 Ω (according to UL60065); 200 W, 25 Ω (according to UL2572); 200 W, 25 Ω (according to CAN/ULC-S576 with separate UPS); 100 W, 50 Ω (according to CAN/ULC-S576); (All total of Speaker output 1 – 6 and Direct Output) ← **fuller than the datasheet's bare "240 W"; the standards-referenced derates are published only here**
  • Frequency Response: 50 Hz – 20 kHz, ±3 dB (at 1/3 rated output), 800 Hz – 2.8 kHz (according to UL2572); 400 Hz – 4 kHz (according to CAN/ULC-S576)
  • Distortion: Under 0.7% (at rated output, 1 kHz)
  • S/N Ratio: Over 85 dB
  • Input (differs): "External AMP Input: 70 V line, removable terminal block (14 pins)" ← **datasheet says 100 V line**
  • Output (differs): "Speaker output 3 – 6: Max. (100 W) per output" ← **datasheet says 120 W**; "Speaker output 1 – 6: Total within rated output"; "Allowable minimum load: 245 Ω (20 W) at 70 V line for speaker line failure detection" ← **datasheet says 500 Ω (20 W) at 100 V line**; additionally "Ground faults detection: 0 Ω" and "Wire to wire faults detection: 0 Ω" (not in the datasheet)
  • 22 V DC Output (differs): "22 V DC Special Application, Maximum feeding current 0.3 A (for RM-200M only)" ← **datasheet row is "DC24V Output: 24 V DC, Maximum feeding current 0.3 A"**
  • Operating Temperature (differs): 0 to 49°C (32 to 120°F) ← **datasheet says -5 °C to +45 °C (23 °F to 113 °F)**
  • Finish: Panel: Aluminum, hair-line, black; Case: Surface-treated steel plate, black, paint
  • Dimensions: 482 (W) × 132.6 (H) × 431.2 (D)mm (18.98" x 5.22" x 16.98") (agrees)
  • Weight: 16.5kg (36.38 lbs) (agrees)
  • Accessories (differs in order/wording): AC power cord (2m) × 1, Emergency microphone × 1, Plastic foot × 4, Plastic foot mounting screw × 4, Removable terminal plug (14 pins) × 3, Removable terminal plug (16 pins) × 1, Link cable (3m) × 2, Setting software (CD) × 1
  • Option: Input transformer: IT-450
  • UL Certified: UL 2572 and CAN/ULC-S576

Specifications

Technical
Model VM-3240VA
Order Code VM-3240VA AMQ
Power Source 120 V AC, 60 Hz
Power Consumption Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) ["Power Consumption" is duplicated inside the value as printed]
Rated Output 240 W
Frequency Response 50 Hz - 20 kHz, ±3 dB (at 1/3 rated output)
Distortion 0.7 % or less (at rated output, 1 kHz)
Signal-to-Noise Ratio 85 dB or more
Audio Input/Output Characteristic Sampling frequency: 48 kHz; A/D D/A converter: 24 bit
Input Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack; Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins); BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack; External amplifier input: 100 V line, removable terminal block (14 pins)
Output Speaker output 1 - 2: Max. (240 W) per output; Speaker output 3 - 6: Max. (120 W) per output; Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins); Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection; Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins); Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
RM Link Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector; Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Network I/F 10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector; Maximum distance: 100 m (109.36 yd) between this unit and a switching hub; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
VM Link Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector; Maximum distance: 800 m (874.89 yd); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
EXT PA Link Connecting the VP-2241 or VP-2421, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
General Control Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins); Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins)
Emergency Control Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector; Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector; Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector
ATT Control Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins)
Power Input/Output Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC); PS out: 28 V DC/18 A; M4 screw terminal, distance between barriers: 11 mm (0.43")
DC24V Output 24 V DC, Maximum feeding current 0.3 A
DS Link Connecting the VX-2000DS, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
Operating Temperature -5 °C to +45 °C (23 °F to 113 °F)
Operating Humidity 5 % to 95 %RH (no condensation)
Included Accessories Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1
Power Source 120 V AC, 60 Hz (agrees)
Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) (agrees)
Rated Output 240 W, 21 Ω (according to UL60065); 200 W, 25 Ω (according to UL2572); 200 W, 25 Ω (according to CAN/ULC-S576 with separate UPS); 100 W, 50 Ω (according to CAN/ULC-S576); (All total of Speaker output 1 – 6 and Direct Output) ← **fuller than the datasheet's bare "240 W"; the standards-referenced derates are published only here
Frequency Response 50 Hz – 20 kHz, ±3 dB (at 1/3 rated output), 800 Hz – 2.8 kHz (according to UL2572); 400 Hz – 4 kHz (according to CAN/ULC-S576)
Distortion Under 0.7% (at rated output, 1 kHz)
S/N Ratio Over 85 dB
Input (differs) "External AMP Input: 70 V line, removable terminal block (14 pins)" ← **datasheet says 100 V line
Output (differs) "Speaker output 3 – 6: Max. (100 W) per output" ← **datasheet says 120 W**; "Speaker output 1 – 6: Total within rated output"; "Allowable minimum load: 245 Ω (20 W) at 70 V line for speaker line failure detection" ← **datasheet says 500 Ω (20 W) at 100 V line**; additionally "Ground faults detection: 0 Ω" and "Wire to wire faults detection: 0 Ω" (not in the datasheet)
22 V DC Output (differs) "22 V DC Special Application, Maximum feeding current 0.3 A (for RM-200M only)" ← **datasheet row is "DC24V Output: 24 V DC, Maximum feeding current 0.3 A"
Operating Temperature (differs) 0 to 49°C (32 to 120°F) ← **datasheet says -5 °C to +45 °C (23 °F to 113 °F)
Accessories (differs in order/wording) AC power cord (2m) × 1, Emergency microphone × 1, Plastic foot × 4, Plastic foot mounting screw × 4, Removable terminal plug (14 pins) × 3, Removable terminal plug (16 pins) × 1, Link cable (3m) × 2, Setting software (CD) × 1
Option Input transformer: IT-450
UL Certified UL 2572 and CAN/ULC-S576
Physical
Finish Panel: Aluminum, hairline, black; Case: Surface-treated steel plate, black, paint
Dimensions 482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98")
Weight 16.5 kg (36.38 lb)
Finish Panel: Aluminum, hair-line, black; Case: Surface-treated steel plate, black, paint
Dimensions 482 (W) × 132.6 (H) × 431.2 (D)mm (18.98" x 5.22" x 16.98") (agrees)
Weight 16.5kg (36.38 lbs) (agrees)
Supplied Accessories The VM-3240VA is the system's main/controlling unit. Per the brochure, a maximum system comprises 1× VM-3240VA plus 9× VM-3240E, giving max. 13 MIC/LINE inputs and max. 60 assignable speaker zone outputs (6 outputs per amplifier); VM Link output connects the VM-3240E or VM-3360E extension amplifiers (max. 800 m); Power in / DS Link connect the VX-2000DS Emergency Power Supply only; EXT PA Link connects the VP-2241 or VP-2421 power amplifier; RM Link connects RM-300MF / RM-200M remote and fireman's microphones; Option: IT-450 input transformer

Specifications subject to change.

Downloads

Product Page

Specification Sheet (PDF)

Series Brochure (PDF)

Product image