Description
TOA VM-3240VA AMQ Voice Alarm System Master 240W w/UL 2572/864
Product Details
The VM-3240VA is the 240 W voice alarm system amplifier and controlling unit of the VM-3000 Series, certified to UL 2572 and CAN/ULC-S576.
It has four mic/line inputs, two BGM inputs, six speaker outputs, two remote microphone links, a network port and eight control inputs and outputs. A system takes up to nine VM-3240E extension amplifiers. Power is 120 V AC, 60 Hz. It measures 482 × 132.6 × 431.2 mm and weighs 16.5 kg. A hand-held emergency microphone, setting software CD and link cables are supplied.
Features
- Max. 13 MIC/LINE Inputs
- Max. 60 assignable speaker zone outputs
- Up to a combination of 4 Fireman's and remote Microphones
- Continuous speaker line monitoring without interruption
- Complete fault detection and indication
- Built-in voice alarm message
- Max. 13 MIC/LINE Inputs (Max system comprises 1x VM-3240VA: 4 MIC/LINE Inputs, 9x VM-3240E: 9 Local Inputs)
- 2 BGM inputs - VM-3240VA
- Up to a combination of 4 Fireman's and remote Microphones (max. 2 Fireman's Microphones)
- Max. 60 assignable speaker zone outputs (6 outputs per amplifier)
- BGM volume setting possible for each zone
- Digital audio processed & controlled
- Full digital audio mixing (DSP)
- Built-in high quality electronic voice message
- Intuitive configuration
- Zone setting, priority setting, failure detection setting by dedicated PC software
- LCD display of current status and configuration setting of system units
- Emergency Functions: Continuous speaker line monitoring without interruption of BGM distribution or paging announcements; Complete fault detection and indication; Off-site log check capability via LAN; Built-in and remote Fireman's Microphones; Built-in voice alarm message; 2-Phased voice alarm message (Alert and Evacuation) broadcasting
- Paging Functions: 2 Remote Microphone interface lines; Paging (All zones/Group/Individual); 2-channel broadcast with external amplifier (Paging/BGM), VP-2241 (240W x 1) Power Amplifier
- Power Source: 120 V AC, 60 Hz
- Power Consumption: Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) ["Power Consumption" is duplicated inside the value as printed]
- Rated Output: 240 W
- Frequency Response: 50 Hz - 20 kHz, ±3 dB (at 1/3 rated output)
- Distortion: 0.7 % or less (at rated output, 1 kHz)
- Signal-to-Noise Ratio: 85 dB or more
- Audio Input/Output Characteristic: Sampling frequency: 48 kHz; A/D D/A converter: 24 bit
- Input: Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack; Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins); BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack; External amplifier input: 100 V line, removable terminal block (14 pins)
- Output: Speaker output 1 - 2: Max. (240 W) per output; Speaker output 3 - 6: Max. (120 W) per output; Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins); Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection; Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins); Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack
- RM Link: Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector; Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
- Network I/F: 10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector; Maximum distance: 100 m (109.36 yd) between this unit and a switching hub; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
- VM Link: Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector; Maximum distance: 800 m (874.89 yd); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
- EXT PA Link: Connecting the VP-2241 or VP-2421, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
- General Control: Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins); Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins)
- Emergency Control: Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector; Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector; Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector
- ATT Control: Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins)
- Power Input/Output: Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC); PS out: 28 V DC/18 A; M4 screw terminal, distance between barriers: 11 mm (0.43")
- DC24V Output: 24 V DC, Maximum feeding current 0.3 A
- DS Link: Connecting the VX-2000DS, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
- Operating Temperature: -5 °C to +45 °C (23 °F to 113 °F)
- Operating Humidity: 5 % to 95 %RH (no condensation)
- Finish: Panel: Aluminum, hairline, black; Case: Surface-treated steel plate, black, paint
- Dimensions: 482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98")
- Weight: 16.5 kg (36.38 lb)
- Included Accessories: Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1
- Power Source: 120 V AC, 60 Hz (agrees)
- Power Consumption: 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) (agrees)
- Rated Output: 240 W, 21 Ω (according to UL60065); 200 W, 25 Ω (according to UL2572); 200 W, 25 Ω (according to CAN/ULC-S576 with separate UPS); 100 W, 50 Ω (according to CAN/ULC-S576); (All total of Speaker output 1 – 6 and Direct Output) ← **fuller than the datasheet's bare "240 W"; the standards-referenced derates are published only here**
- Frequency Response: 50 Hz – 20 kHz, ±3 dB (at 1/3 rated output), 800 Hz – 2.8 kHz (according to UL2572); 400 Hz – 4 kHz (according to CAN/ULC-S576)
- Distortion: Under 0.7% (at rated output, 1 kHz)
- S/N Ratio: Over 85 dB
- Input (differs): "External AMP Input: 70 V line, removable terminal block (14 pins)" ← **datasheet says 100 V line**
- Output (differs): "Speaker output 3 – 6: Max. (100 W) per output" ← **datasheet says 120 W**; "Speaker output 1 – 6: Total within rated output"; "Allowable minimum load: 245 Ω (20 W) at 70 V line for speaker line failure detection" ← **datasheet says 500 Ω (20 W) at 100 V line**; additionally "Ground faults detection: 0 Ω" and "Wire to wire faults detection: 0 Ω" (not in the datasheet)
- 22 V DC Output (differs): "22 V DC Special Application, Maximum feeding current 0.3 A (for RM-200M only)" ← **datasheet row is "DC24V Output: 24 V DC, Maximum feeding current 0.3 A"**
- Operating Temperature (differs): 0 to 49°C (32 to 120°F) ← **datasheet says -5 °C to +45 °C (23 °F to 113 °F)**
- Finish: Panel: Aluminum, hair-line, black; Case: Surface-treated steel plate, black, paint
- Dimensions: 482 (W) × 132.6 (H) × 431.2 (D)mm (18.98" x 5.22" x 16.98") (agrees)
- Weight: 16.5kg (36.38 lbs) (agrees)
- Accessories (differs in order/wording): AC power cord (2m) × 1, Emergency microphone × 1, Plastic foot × 4, Plastic foot mounting screw × 4, Removable terminal plug (14 pins) × 3, Removable terminal plug (16 pins) × 1, Link cable (3m) × 2, Setting software (CD) × 1
- Option: Input transformer: IT-450
- UL Certified: UL 2572 and CAN/ULC-S576
Specifications
| Technical | |
|---|---|
| Model | VM-3240VA |
| Order Code | VM-3240VA AMQ |
| Power Source | 120 V AC, 60 Hz |
| Power Consumption | Power Consumption 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) ["Power Consumption" is duplicated inside the value as printed] |
| Rated Output | 240 W |
| Frequency Response | 50 Hz - 20 kHz, ±3 dB (at 1/3 rated output) |
| Distortion | 0.7 % or less (at rated output, 1 kHz) |
| Signal-to-Noise Ratio | 85 dB or more |
| Audio Input/Output Characteristic | Sampling frequency: 48 kHz; A/D D/A converter: 24 bit |
| Input | Input 1 - 3: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, combined XLR connector (female)/phone jack; Input 4: -50 dB* (MIC)/-10 dB* (LINE) (changeable), 600 Ω, electronically balanced, removable terminal block (14 x 2 pins); BGM 1 - 2: -10 dB*, 10 kΩ, unbalanced, RCA pin jack; External amplifier input: 100 V line, removable terminal block (14 pins) |
| Output | Speaker output 1 - 2: Max. (240 W) per output; Speaker output 3 - 6: Max. (120 W) per output; Speaker output 1 - 6: Total within 240 W, removable terminal block (14 pins); Allowable minimum load: 500 Ω (20 W) at 100 V line for speaker line failure detection; Direct output: Direct output from internal or external amplifier, removable terminal block (16 pins); Recording output BGM/Paging: 0 dB*, 10 kΩ, unbalanced, RCA pin jack |
| RM Link | Input 1 - 2: Connecting the RM-300MF/RM-200M Remote Microphone. RJ45 female connector; Maximum distance: Total 800 m (874.89 yd) between this unit and remote microphones; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
| Network I/F | 10BASE-T / 100BASE-TX (selectable by automatic negotiation), RJ45 female connector; Maximum distance: 100 m (109.36 yd) between this unit and a switching hub; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
| VM Link | Output: Connecting the VM-3240E or VM-3360E, RJ45 female connector; Maximum distance: 800 m (874.89 yd); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
| EXT PA Link | Connecting the VP-2241 or VP-2421, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
| General Control | Input 1 - 8: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, removable terminal block (14 x 2 pins); Output 1 - 8: Isolated open collector output, withstand voltage: 30 V DC, operating current: 10 mA or less, removable terminal block (14 x 2 pins) |
| Emergency Control | Input 1 - 5: No-Voltage make contact input, open voltage: 24 V DC, short-circuit current: 2 mA or less, RJ45 female connector; Input 6: Isolated voltage input, Inactive: -24 V ±20 %, Active: +24 V ±20 %, RJ45 female connector; Status out: Relay contact output, withstand voltage: 40 V DC, operating current: 2 - 300 mA, RJ45 female connector |
| ATT Control | Relay contact 1-6, 125 V AC or 30 V DC, total under 5 A, removable terminal block (16 pins) |
| Power Input/Output | Power in: Connecting the VX-2000DS only (operating range: 20 - 40 V DC); PS out: 28 V DC/18 A; M4 screw terminal, distance between barriers: 11 mm (0.43") |
| DC24V Output | 24 V DC, Maximum feeding current 0.3 A |
| DS Link | Connecting the VX-2000DS, RJ45 female connector; Maximum distance: 5 m (16.4 ft); Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
| Operating Temperature | -5 °C to +45 °C (23 °F to 113 °F) |
| Operating Humidity | 5 % to 95 %RH (no condensation) |
| Included Accessories | Power cable (2 m (6.56 ft) ...1, Setting software-CD ...1, Link cable (3 m (9.84 ft) ...2, Plastic foot ...4, Plastic foot mounting screw ...4, Removable terminal plug (14 pins)...3, Removable terminal plug (16 pins) ...1, Emergency microphone (hand-held type) ...1 |
| Power Source | 120 V AC, 60 Hz (agrees) |
| Power Consumption | 690 VA (at rated output), 260 W (According to UL60065), 63 W (at no signal) (agrees) |
| Rated Output | 240 W, 21 Ω (according to UL60065); 200 W, 25 Ω (according to UL2572); 200 W, 25 Ω (according to CAN/ULC-S576 with separate UPS); 100 W, 50 Ω (according to CAN/ULC-S576); (All total of Speaker output 1 – 6 and Direct Output) ← **fuller than the datasheet's bare "240 W"; the standards-referenced derates are published only here |
| Frequency Response | 50 Hz – 20 kHz, ±3 dB (at 1/3 rated output), 800 Hz – 2.8 kHz (according to UL2572); 400 Hz – 4 kHz (according to CAN/ULC-S576) |
| Distortion | Under 0.7% (at rated output, 1 kHz) |
| S/N Ratio | Over 85 dB |
| Input (differs) | "External AMP Input: 70 V line, removable terminal block (14 pins)" ← **datasheet says 100 V line |
| Output (differs) | "Speaker output 3 – 6: Max. (100 W) per output" ← **datasheet says 120 W**; "Speaker output 1 – 6: Total within rated output"; "Allowable minimum load: 245 Ω (20 W) at 70 V line for speaker line failure detection" ← **datasheet says 500 Ω (20 W) at 100 V line**; additionally "Ground faults detection: 0 Ω" and "Wire to wire faults detection: 0 Ω" (not in the datasheet) |
| 22 V DC Output (differs) | "22 V DC Special Application, Maximum feeding current 0.3 A (for RM-200M only)" ← **datasheet row is "DC24V Output: 24 V DC, Maximum feeding current 0.3 A" |
| Operating Temperature (differs) | 0 to 49°C (32 to 120°F) ← **datasheet says -5 °C to +45 °C (23 °F to 113 °F) |
| Accessories (differs in order/wording) | AC power cord (2m) × 1, Emergency microphone × 1, Plastic foot × 4, Plastic foot mounting screw × 4, Removable terminal plug (14 pins) × 3, Removable terminal plug (16 pins) × 1, Link cable (3m) × 2, Setting software (CD) × 1 |
| Option | Input transformer: IT-450 |
| UL Certified | UL 2572 and CAN/ULC-S576 |
| Physical | |
|---|---|
| Finish | Panel: Aluminum, hairline, black; Case: Surface-treated steel plate, black, paint |
| Dimensions | 482 (W) x 132.6 (H) x 431.2 (D) mm (18.98" x 5.22" x 16.98") |
| Weight | 16.5 kg (36.38 lb) |
| Finish | Panel: Aluminum, hair-line, black; Case: Surface-treated steel plate, black, paint |
| Dimensions | 482 (W) × 132.6 (H) × 431.2 (D)mm (18.98" x 5.22" x 16.98") (agrees) |
| Weight | 16.5kg (36.38 lbs) (agrees) |
| Supplied Accessories | The VM-3240VA is the system's main/controlling unit. Per the brochure, a maximum system comprises 1× VM-3240VA plus 9× VM-3240E, giving max. 13 MIC/LINE inputs and max. 60 assignable speaker zone outputs (6 outputs per amplifier); VM Link output connects the VM-3240E or VM-3360E extension amplifiers (max. 800 m); Power in / DS Link connect the VX-2000DS Emergency Power Supply only; EXT PA Link connects the VP-2241 or VP-2421 power amplifier; RM Link connects RM-300MF / RM-200M remote and fireman's microphones; Option: IT-450 input transformer |
Specifications subject to change.